Description
The D5290S-078 is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508 for high risk industries. It provides isolation between input channel and output contacts.
Three mutually exclusive (by DIP-Switch programming) monitoring circuits are provided:
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold.
3) short circuit fault detection (only for Functional Safety applications with NE Relay condition): when enabled, it allows DCS/PLC to detect short circuit fault of module.
Mounting on standard DIN-Rail or on customized Termination Boards,in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2.
Features
• Systematic capability SIL 3
• Installation in Zone 2 / Division 2.
• 5 A SIL 3 / SIL 2 contacts for NE or ND loads with NE or ND Relay condition.
• Line input monitoring in-field DIP Switch selectable.
• Driving input voltage monitoring.
• Input/Output isolation.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
• ATEX, IECEx, FM, FMC, INMETRO, GOST, TÜV Certifications.
• Type Approval Certificate DNV for marine applications.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards.
Channels
1
SIL level
SIL 3