5 A SIL 3 Relay Output Module for NE Load

Description

The single channel Relay Output D5090S-086 is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2 for high risk industries. It provides isolation between input and output contacts.
Three mutually exclusive (by DIP-Switch programming) monitoring circuits are provided:
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold.
3) short circuit fault detection: when enabled, it allows DCS/PLC to detect short circuit fault of module.

D5090S-086 provides two NC contacts for normally energized load and a NO contact for service purpose, in order to switch the NE load on both supply lines.

Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area or in Zone 2.

Features

• Systematic capability SIL 3
• Installation in Zone 2.
• SIL 3 contact for NE load and contact for service purpose.
• Line input monitoring in-field DIP Switch selectable.
• Driving input voltage monitoring.
• Input/Output isolation.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards.

Supply

24 Vdc nom (21.6 to 27.6 Vdc)

Channels

1

SIL level

SIL 3
Image of D5090S-086 (WEB)

Download

    Datasheet of D5090-086 ( EN | DE | ES | FR | IT | JA | RU | CN )
    D5000 Series Common Specifications and Dimensional Drawing ( EN )
    Instruction Manual D5000-D5200 Series ( EN )
    Ex safety instruction manual for D5000 series ( EN )
    Instruction Manual D5090-086 ( EN )
    ATEX > DEKRA > DEKRA ATEX D5000 Relay Series Certificate ( EN | DE )
    CCC_EX > NEPSI > D5000 CCC certificate for China ( EN )
    EAC_EMC > EAC > D5000/D6000 EAC EMC Declaration of Conformity ( RU )
    EAC_EX > CCVE > EAC Ex Certificate for D5000 Series ( RU )
    EMIRATES_EX > SGS > Emirates Certificate of Conformity D5000 ( EN )
    IECEX > DEKRA > DEKRA IECEx for D5000 Series ( EN )
    INMETRO_EX > DNV-GL > INMETRO Certificate DNV 13.0109 X for D5000 ( EN )
    MARITIME > DNV-GL > DNV Maritime Certificate TAA00001U0 for D5000 series ( EN | EN )
    ORDINARY_LOCATION > UL > UL-cUL D5000 Relays Certificate Ordinary Location ( EN )
    QMS_FS > TUV_SUD > TUV C-IS-236198-09 Functional Safety Certificate ( EN )
    SIL > TUV_SUD > TUV C-IS-236198-04 SIL Certificate Summary ( EN )
    EU Declaration of Conformity for RoHS, REACh ( EN )
    EU Declaration of Conformity for D5000 relays ( EN )
    Declaration of Conformity G3 compliance ( EN )
    2D_drawing_D5000_dwg ( EN )
    3D_drawing_D5000_dwg ( EN )
    3D_drawing_D5000_stp ( EN )
    MCHP196Power Bus Terminal Block Cover and Fix

 

Request a quotation

« Previous: D5090S
D5090S-086
Next: D5090S-102 »