D5096S

5 A SIL 3 NO contact Relay Out Module for NE or F&G/ND Load with open/short circuit diagnostic

Description

The D5096S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed. 2 for high risk industries.
It provides isolation between input and output contacts.
A wide compatibility towards different DCS/PLC is guaranteed: driving line pulse testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
D5096S has 2+2 SPST relay contacts connected in parallel and then in series to avoid spurious trip and to increase availability (see function diagram).
High availability SIL 3 Safety Function for NE load or F&G / ND load is available.
Load is isolated from supply on both polarities: +/AC, -/AC.
Mounting on standard DIN-Rail, with or without Power Bus, or on customized Termination Boards, in Safe Area or in Zone 2.

Features

• Systematic capability SIL 3.
• Installation in Zone 2.
• Compatible with DCS/PLC pulse testing.
• Line and Load short/open circuit detection.
• Presence of load voltage monitoring.
• The fault in the field is directly mirrored to the PLC DO.
• 5 A high availability to avoid spurious trip SIL 3 contacts for NE or F&G/ND load.
• 6 A inrush current at 24 Vdc / 250 Vac.
• Input/Output/Supply isolation.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards.

Supply

24 Vdc nom (18 to 30 Vdc)

Channels

1

SIL level

SIL 3
D5096S - 5 A SIL 3 NO contact Relay Out Module for NE or F&G/ND Load with open/short circuit diagnostic

request a quotation

Download

    DTS0638 D5096S data sheet (English) (PDF 267 KB)
    ISM0121D5000-D5200 Series General Instruction Manual (PDF 3.27 MB)
    ISM0156D5000 Series Safety Instruction Manual (PDF 5.24 MB)
    ISM0301D5096S instruction manual (PDF 413 KB)
    ISM0308D5096S safety manual (PDF 356 KB)
    CRT060ATEX certificate n. BVS 10 ATEX E 114 X (PDF 8.11 MB)
    CRT062IECEx CoC for D5000 Series [link IECEx BVS 10.0072X] (PDF 8.31 MB)
    CRT130TÜV SIL Functional Safety Certificate (PDF 65 KB)
    CRT214TÜV SIL Certificate Summary (PDF 501 KB)
    CRT243TRCU Certificate for D5093, D5094, D5095, D5096, D5097, D5295 Series (PDF 1.26 MB)
    JDFT04912mm DIN Rail Connector
    MCHP196Power Bus Terminal Block Cover and Fix
    MOR017Plug-in Terminal Block male, Horizontal Output, for Bus Power
    MOR022Plug-in Terminal Block female, Horizontal Output, for Bus Power
Are you interested in this product? Request a quotation, search for an expert in your area or contact us.

« Previous: D5095S
D5096S