D1063S

1 Ch, Load Cell / Strain Gauge Bridge Isolating Repeater

Description

The single channel DIN Rail Load Cell/Strain Gauge Bridge Isolating Repeater D1063S acts as a transparent galvanic isolated interface installed between a weighing indicator in Safe Area and a load cell (or group of load cells) in Hazardous Area; it appears at the terminals of the indicator as a single load cell equivalent to the one in the field. Provides a fully floating power supply voltage with remote sensing capability to load cell located in Hazardous Area and repeats, while isolating, the mV signal output to drive a load in Safe Area depending on the host system reference voltage. Up to four 350 Ω load cells, or six 450 Ω load cells, or twelve 1000 Ω load cells can be connected in parallel. Voltage reference (Safe Area side) is DIP switch configurable to select internal or external (host system) supply. In addition a field wiring fault red LED indicates any wire break in the Hazardous Area side.

Features

• Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
• Strain Gauge Bridge Transparent Repeater.
• Up to four 350 Ω load cells in parallel or up to six 450 Ω load cells in parallel or up to twelve 1000 Ω load cells in parallel.
• Broken field wire fault detection.
• High Accuracy.
• Three port isolation, Input/Output/Supply.
• EMC Compatibility to EN61000-6-2, EN61000-6-4.
• In-field programmability by DIP switch.
• High Reliability, SMD components.
• Simplified installation using standard DIN Rail and plug-in terminal blocks.
• 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.

Supply

24 Vdc nom (20 to 30 Vdc)

Channels

1
D1063S - Load Cell/Strain Gauge Bridge Isolating Repeater

request a quotation

Download

    DTS0185 D1063S data sheet (English) (PDF 355 KB)
    ISM0069D1063S instruction manual (PDF 471 KB)
    ISM0102General D1000 Series Instruction Manual (PDF 2.39 MB)
    ISM0155General D1000 Series Safety Instruction Manual (PDF 3.35 MB)
    CRT007ATEX certificate n. Presafe 16ATEX8917 (I.S.) (PDF 489 KB)
    CRT014Metrological Certificate for D1000 Series (Russia) (PDF 779 KB)
    CRT020FM 3024643 (USA) & FM-C 3029921C (Canada) (PDF 3.42 MB)
    CRT028Korean Register Type Approval Certificate (PDF 577 KB)
    CRT033IECEx CoC for D1054S, D1061S, D1063S (I.S.) [link IECEx PRE 16.0084] (PDF 308 KB)
    CRT047ATEX certificate n. IMQ 09 ATEX 013 X (non-sparking) (PDF 160 KB)
    CRT125IECEx CoC for D1000 Series (non-sparking) [link IECEx IMQ 13.0011X] (PDF 60 KB)
    CRT162INMETRO Certificate DNV 13.0135 (PDF 531 KB)
    CRT179DNV Maritime Type Approval Certificate (D1000 Series) (PDF 2.06 MB)
    CRT192TRCU Certificate for D1000 Series (PDF 3.15 MB)
    CRT216Ukraine certificate for D1000 series (PDF 3.50 MB)
    APN0007Universal AC Power Supply for Series D1000 (PDF 44 KB)
    BUSPower Bus Optional Enclosure
    CABF012Dedicated cable for load cell 3x2x1 mm2 with 3+overall screen
    MCHP065Din Rail Anchor, for Terminal Block Side of Bus Power
    MOR016DIN Rail End Stopper Terminal Block
    MOR017Plug-in Terminal Block male, Horizontal Output, for Bus Power
    MOR022Plug-in Terminal Block female, Horizontal Output, for Bus Power
    PPC1092D1000 Series Serial Adapter Configurator.
    USBADAPTRS-232 to USB Adapter.
Are you interested in this product? Request a quotation, search for an expert in your area or contact us.

« Previous: D1062S
D1063S
Next: D1064S »