D1061S-077 G.M. International s.r.l.
GM International

D1061S-077
RS422 / RS485 Fieldbus Isolating Repeater DIN-Rail Model D1061S-077

The DIN-Rail RS422 / RS485 Fieldbus Isolating Repeater type D1061S-077 is used to separate Intrinsically Safe RS422 / RS485 equipment located in Hazardous Area from a RS232 / RS422 / RS485 controller located in Safe Area. Transmission speed is DIP-switch adjustable from 1.2 Kbit/s up to 1.5 Mbit/s. Terminating impedance is DIP-switch selectable inside the unit (200 Ω value) for both sides of communication lines (Hazardous Area and Safe Area side). RS422 / RS485 connection in Safe Area is provided both on terminal block and SUB D 9 poles female connector on the unit. RS232 connection is provided on SUB D 9 poles female connector only. The module also provides a shield terminal block for connecting cable shielding on Hazardous Area side.

FEATURES

  • Input/Output from Zone 0 (Zone 20), installation in Zone 2.
  • RS422 / RS485 Hazardous Area I.S. Signal.
  • RS232 / RS422 / RS485 Safe Area Signal.
  • Transmission speed up to 1.5 Mbit/s.
  • Three port isolation, Input/Output/Supply.
  • EMC Compatibility to EN61000-6-2, EN61000-6-4.
  • In-field programmability by DIP Switch.
  • 250 Vrms (Um) max. voltage allowed to the Instruments associated with the barrier.

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Current Consumption 100 mA with 1.5 Mbit/s transmission speed, typical.
Power Dissipation 2.0 W with 24 V supply and 1.5 Mbit/s transmission speed typical.
Max. power consumption at 30 V supply and 1.5 Mbit/s transmission speed, 2.8 W.

Input/Output I.S. Hazardous Area

Type RS422 / RS485 Intrinsically Safe connection (EIA RS422-A and EIA RS485 applicable standard).
Terminating impedance 200 Ω DIP-switch selectable.
Transmission speed 1.2, 2.4, 4.8, 9.6, 14.4, 19.2, 38.4, 57.6, 93.75, 115.2, 187.5, 375, 500, 750 Kbit/s or 1.0, 1.5 Mbit/s DIP-switch configurable.
Transmission cable length ≤ 1200 m up to 93.75 Kbit/s, ≤ 1000 m up to 187.5 Kbit/s, ≤ 400 m up to 500 Kbit/s, ≤ 200 m up to 1.5 Mbit/s.
Connection by plug-in disconnect screw terminal block to accomodate terminations up to 2.5 mm2, shield terminal block provided for cable connection.

Output/Input Safe Area

Type RS232 / RS422 / RS485 connection (EIA RS232-C, EIA RS422-A and EIA RS485 applicable standard).
RS422 / RS485 Terminating impedance 200 Ω DIP-switch selectable.
RS422 / RS485 Transmission speed 1.2, 2.4, 4.8, 9.6, 14.4, 19.2, 38.4, 57.6, 93.75, 115.2, 187.5, 375, 500, 750 Kbit/s or 1.0, 1.5 Mbit/s DIP-switch configurable.
RS422 / RS485 Transmission cable length ≤ 1200 m up to 93.75 Kbit/s, ≤ 1000 m up to 187.5 Kbit/s, ≤ 400 m up to 500 Kbit/s, ≤ 200 m up to 1.5 Mbit/s.
RS422 / RS485 Connection by plug-in disconnect screw terminal block to accomodate terminations up to 2.5 mm2 or SUB D 9 poles female connector (requires SUB D 9 poles male mating connector), DIP-switch configurable.
RS232 Transmission speed 1.2, 2.4, 4.8, 9.6, 14.4, 19.2, 38.4, 57.6, 93.75, 115.2 Kbit/s DIP-switch configurable.
RS232 Transmission cable length ≤ 15 m up to 115.2 Kbit/s.
RS232 Connection SUB D 9 poles female connector (requires SUB D 9 poles male mating connector).

Isolation

Test Voltage I.S. RS422-RS485 / RS232-RS422-RS485 1.5 KV; I.S. RS422-RS485 / Supply 1.5 KV; RS232-RS422-RS485 / Supply 500 V.

Environmental conditions

Operating temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.
Storage temperature limits – 45 to + 80 °C.

Safety description

Safety parameters Uo/Voc = 3.7 V, Io/Isc = 93 mA, Po/Po = 85 mW at terminals 13-14 and 15-16. Ui/Vmax = 30 V, Ii/Imax = 136 mA, Ci = 0 nF, Li = 0 nH at terminals 13-14 and 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.

Mounting

Type EN/IEC60715 TH 35 DIN-Rail.
Weight about 170 g.
Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2 and SUB D 9 poles (DB9) DIN 41652 female connector (only for RS232, RS422, RS485 Safe Area connection).
Location Safe Area or Zone 2, Group IIC T4 installation.
Protection class IP 20.
Dimensions Width 22.5 mm, Depth 99 mm, Height 114.5 mm.

Data Sheet


Datasheet of D1061-077 ( EN )
D1000 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual D1061-077 ( EN )
Instruction Manual D1000 Series ( EN | RU )
Ex safety instruction manual for D1000 series ( EN | IT )
INMETRO safety instruction manual for D1000 series ( PT )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D1000 Series English Certificate ( EN ) Europe DMT 01 ATEX E 042 X DEKRA 2022-04-25
EMC D1000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.НХ37.В.06311/20 EUROCERT 2020-08-13
Ex EAC Ex Certificate for D1000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.НА67.В.00113/20 TECHNOPROGRESS 2020-09-04
Ex INMETRO Certificate DNV 13.0108 X for D1000 series ( EN ) Brazil DNV 13.0108 X DNV 2022-12-10
IECEx DEKRA IECEx for D1000 Series ( EN ) International IECEx BVS 07.0027X DEKRA 2022-05-30
Maritime KR Maritime Certificate D1000 Series ( EN ) International MIL20769-EL001 KR 2022-07-04

Declarations of Conformity


EU Declaration of Conformity for D1048, D1049, D1061-077 ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of G3 compliance for D1000_PSD1000-PSD1001-PSD1001C-PSD1004-PSD1220-PSD1220-098 SERIES ( EN )

Dimensions


Image of D1061S-077_size

Connections


Drawings


2d_drawing_D1000_dwg ( EN )
3d_drawing_D1000_dwg ( EN )
3d_drawing_D1000_stp ( EN )