5700 G.M. International s.r.l.
GM International

5700
SIL 3 HART® Mux Modem for Termination Board

The HART® Multiplexer Modem interfaces up to 256 smart devices (transmitters, I/P, proportional valves, etc…) in a HART® Network. Each device can be fully identified, configured and monitored either by a remote PC running an FDT-based software package (PACTware™, etc...) through a dedicated Device Type Manager (DTM), by HART® OPC Server, or by a specific asset management system. Up to 63 Multiplexer Modem (16128 loops) can be connected in multi-drop mode to the PC through the RS485 HART® Protocol, whose baudrate can be configured via software. The module is intended to be mounted on the following Term. Boards:
- TB(E)-D5001-HRT-003: to be used with GMI AI/AO Term. Boards;
- TB(E)-D5001-HRT-004: to be used with DIN-Rail mounted barriers/isolators or direct field connections, 4-20 mA loop signals, AI card impedance = 250 Ω;
- TB(E)-D5001-HRT-005: to be used with DIN-Rail mounted barriers/isolators or direct field connections, 1-5 V loop signals;
- TB(E)-D5001-HRT-006: to be used with DIN-Rail mounted barriers/isolators or direct field connections, 4-20 mA loop signals, AI card impedance = 100÷150 Ω;
- TB(E)-D5001-HRT-007: to be used with DIN-Rail mounted barriers/isolators or direct field connections, 4-20 mA loop signals,
AI card impedance = 0÷50 Ω.
Termination board types can be combined to manage different interfaces at the same time, provided the maximum number of channels is not exceeded.
The HART® Multiplexer Modem is SIL 3 certified as non-interfering with the signal loops.

FEATURES

  • SIL 3 / SC 3
  • Installation in Zone 2/Div. 2
  • Up to 256 channels (extendable to 16128 with 63 multi-drop units)
  • HART® RS-485 interface to access field smart devices
  • Three port isolation, Field Interface/Serial Interface/Supply
  • Simplified installation on custom Termination Boards

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

256

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (18 to 30 Vdc) reverse polarity protected, provided through Termination Board.
Current Consumption 20 mA @ 24 Vdc typical (modem only), 40 mA @ 24 Vdc in full topology (with maximum number of extension boards), typical.
Power Dissipation 0.5 W @ 24 Vdc typical (modem only), 1 W @ 24 Vdc in full topology (with maximum number of extension boards), typical.

Field Interface

Number of channels 256.
HART® field device revision 5 to 7.

Write Protection

Type The HART® Multiplexer Modem 5700 can be protected against writing by shorting terminals 7 and 8.

Serial Interface

Type RS-485 differential pair and grounding.
Topology multi-drop, master/slave connection.
Address 0 - 62, software configurable.
Baud rate from 1200 to 115200 bps, software configurable.

Isolation

Type Field Interface/Serial Interface 500 V; Field Interface/Supply 500 V; Supply/Serial Interface 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Max altitude 2000 m a.s.l.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type on custom Term. Board.
Weight about 100 g.
Location installation in Safe Area or Zone 2, Group IIC T4, or Class 1, Div. 2, Group A, B, C, D, T4.
Connection Width 235 mm, Depth 135 mm, Height 154 mm.
Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of Hart Mux 5700 ( EN | PT | FR | JA | CN | DE | ES | IT )
D5000 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual HART Mux modem 5700 ( EN | RU )
Instruction Manual SWC5090 ( EN | RU )
Safety Manual 5700-xxx + TB-D5001-HRT-003, -004, -005, -006, -007 ( EN )
ATEX safety instruction manual for D5000 series ( EN | IT )

Certifications


Type Description Area Number Issued by Issue Date
ATEX UL ATEX 5700, TBE-D5001-HRT-003, TBE-D5001-HRT-xxx series English Certificate ( EN ) Europe UL 20 ATEX 2492X UL 2021-02-25
EMC 5700 and TB EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.АЖ38.В.00125/19 EUROCERT 2019-05-30
Ex UL-cUL 5700 Divisions ( EN ) North America E519244-2021-02-26 UL 2021-03-17
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx UL IECEx 5700, TBE-D5001-HRT-003, TBE-D5001-HRT-xxx series English Certificate ( EN ) International IECEx ULD 20.0042X UL 2021-02-25
SIL TUV C-IS-272994-01 SIL Certificate Summary ( EN ) International C-IS-272994-01 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity for 5700, TBE-D5001-HRT-xxx ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of 5700_size

Connections


Drawings


2d_drawing_D5000_dwg ( EN )
3d_drawing_D5000_dwg ( EN )
3d_drawing_D5000_stp ( EN )

Software


DTM5700 - Device Type Manager for 5700 HART® Mux ( EN )
SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( EN )
Instruction Manual SWC5090 ( EN )

RELATED PRODUCTS


ACCESSORIES